OW-IO-AI4-420

Quad Analog Input (4-20 mA)

OW-IO-AI4-420
OW-IO-AI4-420
OW-IO-AI4-420

63.90 €

incl. 19% VAT
plus Shipping

Can ship immediately
Product No.: 72496
Description
Specifications
Downloads
Description
The 1-Wire Quad (4 Channel) Input device offers an innovative way to monitor up to 4 analog points. In addition to the voltage reading, each point maintains a minimum value and a maximum value. High/low alarms may also be set independently for each input.

The 1-Wire Quad Input also includes an LED and conditional search support. Additionally, an optional latching relay provides further flexibility for alarm notifications and control applications. These features combine to offer a flexible and efficient system for monitoring and controlling numerous data points throughout a 1-Wire network. The conditional search support allows a host adapter to quickly identify whether any alarm parameters have been met; and the LED and optional latching relay can be configured to behave in a variety of ways:

  • Activate when an alarm becomes active and automatically deactivate when the alarm is cleared.
  • Activate when within alarm parameters and deactivate when within normal range.
  • Independently controlled

The nearly instantaneous automated responses made by the LED and optional relay allow appropriate reactions (activate fan/alarm siren/etc) to occur before the monitoring application is even aware of an alarm. The Quad input has been designed to simplify the reading and controlling process; and therefore any general-purpose 1-Wire host adapter is able to read the analog points. All of the data is contained in five 32 byte memory pages which are updated in real-time. More in-depth information on the memory format is available within the datasheet.

Features


  • Four 16-Bit analog input channels
  • 0-10V and 4-20mA options available
  • Static protected inputs
  • Readings include minimum, maximum, peak and alarm values
  • Uses 1-Wire Communication Protocol
  • Supports Conditional Search with user-selectable conditions
  • Compatible with all general purpose 1-Wire host adapters
  • Pass-through connector for easy daisy-chaining of sensors
  • Optional Relay may be controlled independently or by alarm status
  • Applications include thermostatic controls, industrial systems, flow meters, consumer products, or any system in which discrete control or monitoring is necessary

* The time from a change in input voltage to viewing the result on a computer consists of many delays in addition to the conversion time (i.e. time to read the device on the 1-wire bus, computer processing time). Alarms, peak, minimum and maximum values are computed for each reading, so these parameters have an update rate of 4 * 120ms = 480ms.

** Input currents outside this range is permitted, but will not read correctly.
Specifications
1-Wire ConnectionScrew-Down
Inputs4
Latching RelayNo
Operating Range-40 to 85°C
Supply Voltage4-18 Volts DC
Active Current (5V DC, LED On)16.2 mA
Standby Current (5V DC)8.4 mA
Dimensions (LxWxH)81x48x23 mm
Converter16 Bits
Conversion time* (per channel)120 Milliseconds
Input Voltage (before clamping)-3 to 13 Volts
Input Current**0 to 31.995 mA
Precision0.4% (Full Scale)
Downloads

Last viewed items

Icon Top